Abstract
To mitigate forced oscillation and avoid confusion with modal oscillation, fundamentals of forced oscillation in multimachine power system are investigated. First, the explicit formulation of the oscillation is formulated in terms of forced disturbances and system mode shapes. Then, forced oscillation amplitude, components and envelope are intensively studied. Consequently, measures for mitigating the oscillation are obtained. Forced oscillation can also be effectively detected and discriminated from modal oscillation by utilizing its uniqueness of components properties and envelope shapes. Study results of the 10-machine 39-bus New England test system and a real-life power system demonstrate the correctness of theoretical analyses and effectiveness of detection methods for forced oscillation.
| Original language | English |
|---|---|
| Article number | 7491371 |
| Pages (from-to) | 1149-1160 |
| Number of pages | 12 |
| Journal | IEEE Transactions on Power Systems |
| Volume | 32 |
| Issue number | 2 |
| DOIs | |
| State | Published - Mar 2017 |
Keywords
- Beat frequency oscillation
- eigen-analysis
- envelope
- Forced oscillation
- low frequency oscillation
- resonance
Fingerprint
Dive into the research topics of 'Analysis and Detection of Forced Oscillation in Power System'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver