Abstract
For grid-connected microgrids with high penetration of photovoltaic (PV) generation, overvoltage caused by reverse power flow is a major factor that limits PV power output. To tackle the challenge, this paper proposes a new online overvoltage prevention (OOP) control strategy to maintain PV terminal voltages within specified range while maximizing the PV energy yields. The proposed method is based on a precise active power limit prediction using the dynamic Thevenin equivalent. The active power output of PV array can be modulated in real time such that the voltage at a point of interconnection (POI) is always maintained within a specified range without triggering overvoltage protection. Simulation results using the IEEE 33-bus single-phase test system and IEEE 34-bus three-phase system have validated the effectiveness and accuracy of the proposed control method.
| Original language | English |
|---|---|
| Article number | 6377253 |
| Pages (from-to) | 2071-2078 |
| Number of pages | 8 |
| Journal | IEEE Transactions on Smart Grid |
| Volume | 3 |
| Issue number | 4 |
| DOIs | |
| State | Published - 2012 |
Keywords
- Distribution system
- microgrid
- overvoltage prevention
- photovoltaic generator
- thevenin equivalent
Fingerprint